Page 97
11. Electrical Characteristics
Size
35M-53M
70M
88M 105M
OUDOOR UNIT
POWER
Phase 1-phase 1-phase 1-phase 1-phase
Frequency and
Voltage
220-240V, 50Hz 220-240V, 50Hz 220-240V, 50Hz 220-240V, 50Hz
Power Wiring
(mm
2
)
3×1.5 3×2.5 3×2.5 3×4.0
Circuit Breaker/
Fuse (A)
25/20 25/20 50/40 50/40
Indoor/Outdoor
Connecting
Wiring
Weak Electric
Signal)(mm
2
)
Strong Electric
Signal(mm
2
)
4×1.0(4x2.5 with
auxiliary electric
heater)
4×1.0(4x2.5 with
auxiliary electric
heater)
4×1.0(4x2.5 with
auxiliary electric
heater)
4×1.0(4x2.5 with
auxiliary electric
heater)
Size 105T 120M 140T-160T
OUDOOR UNIT
POWER
Phase 3-phase 1-phase 3-phase
Frequency and Voltage 380-415V, 50Hz 220-240V, 50Hz 380-415V, 50Hz
Power Wiring (mm
2
) 5×2.5 3×4.0 5×2.5
Circuit Breaker/ Fuse
(A)
25/20 50/40 32/25
Indoor/Outdoor
Connecting Wiring
Weak Electric Signal)
(mm
2
)
Strong Electric
Signal(mm
2
)
4×1.0(4x2.5 with
auxiliary electric
heater)
4×1.0(4x2.5 with
auxiliary electric
heater)
4×1.0(4x2.5 with
auxiliary electric
heater)