Product Features
Page 124
For some models: The wired controller connects to terminal board, terminal board connects to main control board.
HA HB
HA HB
Terminal board
Wired controller
ENC1
Main control board
CN2
CN40
4
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
4
4) Address setting
HA HB
HA HB
Unit1
Wired controller
HA HB
Unit2
HA HB
Unit16
a. One non-polarity controller can control up to 16 indoor units.
b. When the non-polarity controller is connected to several units, every air-conditioner in network has only one
network address to distinguish each other.
c. Address code of air-conditioner in LAN is set by code switch ENC1(Duct and Ceiling& Floor) or ADSS(Cassette)
of the indoor unit, and the set range is 0-15.
d. Note: The indoor units are controlled at the same time, not independently. The purpose of setting network
address is identify the unit when error occurs.
Putty
Putty
Putty
Trap
Trap
Trap
c
Note: DO NOT allow water to enter the remote control. Use the trap and putty to seal the wires.