Specifications
Page 88
Size
105M/105T
Pipe Length (m)
Cooling 5 15 25 35 50 65 75
Height
differ-
ence
H (m)
Indoor Upper
than Outdoor
30 0.885 0.845 0.805 0.778
20 0.921 0.894 0.854 0.813 0.786
10 0.958 0.931 0.903 0.862 0.822 0.794
5 0.995 0.967 0.940 0.912 0.871 0.830 0.802
0 1.000 0.972 0.945 0.917 0.876 0.834 0.806
Outdoor Upper
than Indoor
-5 1.000 0.972 0.945 0.917 0.876 0.834 0.806
-10 0.972 0.945 0.917 0.876 0.834 0.806
-20 0.945 0.917 0.876 0.834 0.806
-30 0.917 0.876 0.834 0.806
Heating 5 15 25 35 50 65 75
Height
differ-
ence
H (m)
Indoor Upper
than Outdoor
30 0.962 0.943 0.924 0.911
20 0.975 0.962 0.943 0.924 0.911
10 0.987 0.975 0.962 0.943 0.924 0.911
5 1.000 0.987 0.975 0.962 0.943 0.924 0.911
0 1.000 0.987 0.975 0.962 0.943 0.924 0.911
Outdoor Upper
than Indoor
-5 0.992 0.979 0.967 0.954 0.935 0.917 0.904
-10 0.972 0.959 0.947 0.928 0.909 0.896
-20 0.951 0.939 0.921 0.902 0.889
-30 0.932 0.913 0.895 0.882

Table of Contents