7 - REGULATION
UNIT PARAMETER tab 5
530 TStartPump Pump starting time in maintenance
531 DlyPumpC Pump shutdown delay from comp OFF
532 MaxTempC Threshold of COOLING flow rate reduction
533 MinTempH Threshold of HEATING flow rate reduction
534 IstTempC Hysteresis of cooling flow rate reduction
535 IstTempH Hysteresis of heating flow rate reduction
536 MinSignal Pump signal corresponding to the max. flow rate reduction
537 MaxSignal Pump signal corresponding to the nominal flow rate
540 PumpPFCorr Evaporator pump power factor correction 1=500ns
541 TPompaMax Pump max. waiting time before signalling the flow rate alarm
558 PotRes Capacity delivered by the integration resistances
559 LimText Outdoor temperature limit at the compressor operating
560 Tregime Resistance Timeout
561 MaxInteg Max. analogical output value of the integration resistances when they are activated at the same time
of the compressor
562 MinInteg Min. analogical output value of the integration resistances in modulation phase
563 OffsetOnAux Offset on the aux. insertion step
564 TextOnAux Outdoor temperature limit at the auxiliary operating
579 TimeOutCModeI Output time from the automatic control of the system temperature
580 TimeOutCModeS Output time from the automatic control of the DHW temperature
581 TLimiteCool Input water temp.: under it the activation of the compressor in COOL is allowed
582 TLimiteHeat Input water temp.: over it the activation of the compressor in HEAT is allowed
598 OffsetBT1 Evaporator input temp. offset
599 OffsetBT2 Evaporator output temp. offset
600 OffsetBT4 Coil 1 temp. offset
601 OffsetBT7 Electric heater output temp. offset
602 OffsetBWS Water Reset Offset
603 OffsetBT3 Outdoor temp. offset
604 OffsetBP1 High pressure offset
605 OffsetURExt Ext RH Offset
606 OffsetBDL Demand Limit Offset
607 OffsetBQ BQ analogical Offset
608 OffsetBA
609 OffsetBT5 Source input temp. offset
610 OffsetBT6 Storage temp. offset
611 OffsetBP2 Low pressure offset
612 OffsetBT8 Free input Offset
628 OffsetRuggiada Offset to reach at the dew temperature for the setpoint calculation
629 MaxTempRuggiada Max. limit for the dew point