9.4 ELECTRIC DATA
BASE CONFIGURATION (MAXIMUM LOAD)
9 - TECHNICAL INFORMATION
ELECTRICAL DATA 400/3/50+N
F.L.A. - Fan
A
0,84 0,84 0,84 0,84 0,84
F.L.A. - Total
A 4,84 5,99 7,45 8,23 9,99
2,65
13,34
2,65
17,59
F.L.A.
- Compressor
A 4,00 5,15 6,61 7,39 9,15 10,69 14,94
M.I.C. - Value
A
26,84 32,84 46,84 52,34 64,84 76,65 101,65
SIZE 21 25 31 41 51 61 81
F.L.I. - Fan
kW 0,19 0,19 0,19 0,19 0,19
F.L.I. - Total
kW 2,59 3,38 4,09 4,66 5,69
0,61
7,03
0,61
8,85
F.L.I.
- Compressor
kW
2,40 3,19 3,90 4,47 5,50 6,42 8,24
(1) data referred to 230/1/50 voltage
(2) data referred to 400/3/50+N voltage
(3) data referred to the highest step of input available on the additional heating elements
F.L.A. - FULL LOAD CURRENT AT MAX ADMISSIBLE CONDITIONS
F.L.I. FULL LOAD POWER INPUT AT MAX ADMISSIBLE CONDITION
M.I.C. MAXIMUM INRUSH CURRENT
ELECTRICAL DATA 230/1/50
F.L.A. - FULL LOAD CURRENT AT MAX ADMISSIBLE CONDITIONS
F.L.I. - Compressor
kW 2,63 3,22 4,02 4,83
F.L.I. - Fan
kW
0,19 0,19 0,19 0,19
F.L.I. - Total
kW 2,82 3,41 4,21 5,02
M.I.C. - Value
A 58,84 76,84 97,84 108,84
SIZE
21 25 31 41
F.L.A. - Compressor
A 11,95 15,36 19,14 22,18
F.L.A. - Fan
A 0,84 0,84 0,84 0,84
F.L.A. - Total
A 12,79 16,2 19,98 23,02
F.L.I. FULL LOAD POWER INPUT AT MAX ADMISSIBLE CONDITION
M.I.C. MAXIMUM INRUSH CURRENT
CIRCULATING PUMP DATA
F.L.A. - Pump
A 0,95 0,95 1,24 1.,24 1,24
F.L.I. - Pump
kW 0,20 0,20 0,26 0,26 0,26
3,20
0,66
3,20
0,66
ACCESSORY ELECTRICAL DATA
SIZE 21 25 31 41 51 61 81
F.L.A. - Additional heating element 1 A 26,08 26,08 26,08 26,08 -
F.L.A. - Additional heating element 2 A 8,67 8,67 8,67 8,67 8,67
-
8,67
-
8,67
F.L.I. - Additional heating element 3 kW 6,00 6,00 6,00 6,00 6,00 6,00 6,00
ADDITIONAL HEATING ELEMENT DATA
CIRCULATING PUMP DATA
F.L.A. - Pump
A 1,20 1,20 1,20 1,20 1,20
F.L.I. - Pump
kW 0,14 0,14 0,14 0,14 0,14
1,40
0,31
1,40
0,31
HIGH EFFICIENCY ELECTRICAL DATA (VEC/GCEC)
SIZE 21 25 31 41 51 61 81
EXTERNAL FAN DATA
F.L.A. - Fan
A 1,30 1,30 2,10 2,10 2,10
F.L.I. - Fan
kW 0,17 0,17 0,33 0,33 0,33
3,30
0,73
3,30
0,73