Control
SETTING THE SECOND SET POINT FOR HEATING AND COOLING
A second set point, for both COOLING and HEATING operation, can be enabled by digital input.
This function, unless requested when ordering, must first be enabled by an authorised CLIVET service centre. If the function is
enabled, the sequence shown illustrates the phases to be followed for entering the desired set point values. The closing of the remote
contact is used to switch from the normal working set point to the second set point.
1. Configuration menu
2. Parameter setting menu
3. H2O SYSTEM board menu
4. Second cooling set point
5. Second heating set point