Operations sequence
Before starting the unit pump:
Close all vents in the high points of the unit’s
water circuit.
Close all drain shut-off valves in the low points
of the unit’s water circuit
Exchangers
Pumps
collectors
storage tanks
Thoroughly wash the system with clean water:
use the bypass to exclude the exchanger from
the flow (diagram on previous page) fill and
drain the system several times.
Apply additives to prevent corrosion, fouling,
formation of mud and algae.
Fill the system
do not use the unit pump
Conduct a leak test.
Isolate the pipes to avoid heat dispersions and
formation of condensate.
Leave various service points free (wells, vents,
etc).
Neglecting to wash will lead to the filter having to be
cleaned many times and at worst may damage the
exchangers and compressors.
4 WATER CONNECTION
Water connections
Standard: Victaulic type
Option: to weld
UNIT
A
filettare to threadsaldare to weld
A1
A2
impianto - system
A + B : fornito da Clivet - Clivet supplied
o - or
B
A
UNIT impianto - system
A+B: fornito da Clivet - Clivet supplied

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the CLIVET WSAT-YES 18.2-20.2 and is the answer not in the manual?

CLIVET WSAT-YES 18.2-20.2 Specifications

General IconGeneral
BrandCLIVET
ModelWSAT-YES 18.2-20.2
CategoryChiller
LanguageEnglish

Related product manuals