Operations sequence
Before starting the unit pump:
Close all vents in the high points of the unit’s
water circuit.
Close all drain shut-off valves in the low points
of the unit’s water circuit
Exchangers
Pumps
collectors
storage tanks
Thoroughly wash the system with clean water:
use the bypass to exclude the exchanger from
the flow (diagram on previous page) fill and
drain the system several times.
Apply additives to prevent corrosion, fouling,
formation of mud and algae.
Fill the system
do not use the unit pump
Conduct a leak test.
Isolate the pipes to avoid heat dispersions and
formation of condensate.
Leave various service points free (wells, vents,
etc).
Neglecting to wash will lead to the filter having to be
cleaned many times and at worst may damage the
exchangers and compressors.
4 WATER CONNECTION
Water connections
Standard: Victaulic type
Option: to weld