24
WSAN-YES 18.2-35.2
M0ST10N19-00
Addresses 0 - 15 are the addresses of the selected units.
(addresses)*100+240—(addresses)*100+299 , are read only.
Registro di lettura
Adress function notes
240+(Address)*100 Running mode 1 shutdown
2 cooling
3 heating
241+(Address)*100 SILENT mode 1 Standard
2 Silent
3 Super silent
242+(Address)*100 Setpoint
1℃
243+(Address)*100 Setpoint B
1℃
244+(Address)*100 Unit inlet water temperature Twi
1℃
245+(Address)*100 Unit outlet water temperature Two
1℃
246+(Address)*100
Total outlet water temperature Tw
1℃ ; only for the master (0)
Reading and writing register
Address
function notes
101 Double setpoint Enable/Disable 1/0
102 1o setpoint in cooling 5~20°C
103 2o setpoint in cooling 5~20°C
104 1o setpoint in heating 25~55°C
105 2o setpointin heating 25~55°C
106 temperature compensation in cooling Enable/Disable
107 point 1 temperature compensation in cooling 25~30°C
108 point 2 temperature compensation in cooling 35~40°C
109 temperature compensation value in cooling 0~15°C
110 temperature compensation in heating Enable/Disable
111 point1 temperature compensation in heating 0~5°C
112 point2 temperature compensation in heating 15~20°C
113 temperature compensation value in heating 0~15°C
138
Modbus writing enable
disable local control from controller
1 = enabled; 0 = disabled
6 MODBUS
Units in modular configuration