Path: Main Menu / Unit parameters / Ecoshare
Parameters Short description Description
P0655 LNInstalledUnits Number of units installed/connected in Ecoshare 1 – 8
P0656 LNStandByUnits Number of units on standby 0 – 6
P0657
LNOffset Temperature Offset to be added to the unit setpoint
P0658 TypeRegMS Ecoshare adjustment type 0 – 2
P0659 LNAddress
Unit address 1 – 8 ( 1 = MASTER)
P0664
LNOffsetRec Offset for setpoint shift recovery side 0 – 15 °C
P0702
KRegMS
Activates eco share new mode (1 solo su unità multifunzione)
Type C configuration
Parameter P0658:TypeRegMS = 2 e P0702:KRegMS=0
Only the pumps of the units called to operate are activated.
Slave units mode controlled by the Master
The units are controlled only if they have to deliver power.
this value is calculated starting from the setpoint set in the master unit, adding/removing, depending on the
operating mode (cold/hot), an offset that can be parameterised.
Example:
Master Mode = Cold
Setpoint set in the Master = 7.0 °C
Offset = 0.5 °C
Slave 2 (less wear): Setpoint = 7.0 °C
Slave 3 (wear less than Slave 2): Setpoint = 7.5 °C
Master (wear less than Slave 3): Setpoint = 8.0 °C
Slave 1 (more wear): SetPoint = 8.5 °C
Recovery side
The thermal load is distributed by the Master on all the units, thus meeting the optimal step of each unit
prior to activating the next one.
The activation sequence is calculated based on considerations on the optimal distribution of the utility +
recovery load and on the wear of the units (Less wear = unit with priority).
PLEASE NOTE: the distribution of the steps on the circuits of each individual unit is carried out by the
device that manages the internal distribution of the individual unit (this ensures an optimal distribution for
each unit on the various circuits).