Demand limit
Menu accessible only after having entered the password.
Access reserved only to specifically trained personnel.
The parameter modification can cause irreversible damages.
It is possible to limit the absorbed electric power with an external
signal 0-10 Vcc or 4-20mA. The higher the signal is, the lower
the number of compressors available to meet the thermal need.
Only if P0002 En DemandLimit 0
Path: Main menu / Unit parameters / Options
Path: Main menu / Unit parameters / Options
Parameters Short description Description
P0090 TypeDL Inlet signal type: 0=0-10V; 1=4-20mA
Path: Main Menu / Unit parameters / Setpoint
P0200 set demand limit Parameter setting of the value % of demand limit