Parameters Short description Description
P0002 En DemandLimit Enabling Demand Limit: 0 = disabled, 1 = analogic input, 2 = parameter
P0003 En WaterReset Enabling Water reset: 0 = Off, 1 = Cool, 2 = Heat, 3 = Cool and Heat
P0050 En 2SetPoint Enabling 2SetPoint: 0 = Off, 1 = On
P0036 En CompExt Enabling Climatic TExt: 0 = Off, 1 = Cool, 2 = Heat, 3 = Cool and Heat
P0051 PrioritaCmd
Status and machine mode priority: Local [0] = Priority to local commands, BMS [1]
priority to commands from plant supervisor
P0053 En DIOn-Off Enabling remote ON-OFF: 0 = Off, 1 = On
P0090 TypeDL Inlet signal type: 0 = 0-10V; 1 = 4-20mA
P0091 TypeWR Inlet signal type: 0 = 0-10V; 1 = 4-20mA
Compressor casing resistances
Connect the compressor oil heating resistances at least 8 hours
before the compressor is to be started:
at the first unit start-up
after each prolonged period of inactivity
1 Power the heaters: isolator switch on 1 / ON.
2 Check the power consumption of the resistances to make sure
that they are functioning.
3 Start-up the compressor only if the crank-case temperature on
the lower side is be higher than the outside temperature by
at least 10°C .
4 Do not start the compressor with the crankcase oil below
operating temperature.
Voltage
Check that the air and water temperatures are within in the
operating limits.
Start-up the unit.
While the unit is operative, i.e. in stable conditions nearing
operating ones, check:
Power supply voltage
Total absorption of the unit
Absorption of the single electric loads
Options
Menu accessible only after having entered the password. Access
reserved only to specifically trained personnel.
The parameter modification can cause irreversible damages.
Path: Main menu / Unit parameters / Options