P0618
P0616
P0617
Water reset
Menu accessible only after having entered the password.
Access reserved only to specifically trained personnel.
The parameter modification can cause irreversible damages.
It is possible to limit the absorbed electric power with an external signal 0-10 Vcc or 4-20mA.
The setpoint based on the climatic curve and the Water Reset is displayed on the display
Only if P0003: En WaterReset = 1
Path: Main menu / Unit parameters / Options
Path: Main menu / Unit parameters / Options
Parameters Short description Description
P0091 TypeWR Inlet signal type: 0=0-10V; 1=4-20mA
Path: Main Menu / Unit parameters / Water reset
P0616 MaxCWRC Maximum correction to be applied to the setpoint
P0617 SWRMaxC
Value of the WR control signal corresponding to the correction of the set COOL equal
to the parameter P0281
P0618 SWRMinC
Value of the WR control signal corresponding to the correction of the set COOL equal
to 0