IGS-NT-BC, SW Version 1.2.0,   ©ComAp – January 2019                                     
IGS-NT-BC-1.2.0 Reference Guide.PDF 
 
 
Figure: Example of control groups 
 
Once the BTB breaker is closed, the control group 2 and 3 become new group 2+3. The closed BTB and the 
group link function influence the load reserve (i.e. increased by added gen-set of added gen-sets). Load 
sharing applies for all gen-sets.  
Load shedding 
All LOAD SHED outputs are activated (closed) to trip the unessential load when gen-set goes to island: 
a)  When GCB is closed after mains fail and gen-set starts in  SEM / AUT mode. 
b)  When MCB opens from parallel to mains operation in  SEM / AUT mode. 
c)  Before MCB is opened in MAN mode by button. 
 
The load shedding function is active in all controller modes except OFF. 
Load shedding has three steps and each step is linked with its own Load shed x binary output. There is only 
one load shed level and delay for all three steps as well as recon level and delay. Load shed can only move 
from one step to the next, e.g. No LoadShed to LdShed S1 to LdShed S2 to LdShed S3 and vice versa.  
If manual reconnection of the load is desired, the AutoLd recon setpoint needs to be disabled (AutoLd recon 
= DISABLED) and the MAN load recon binary input needs to be configured. 
Rising edge on this input resets the controller to a lower stage, but only if the load is under the Ld recon level 
at that moment. 
 
HINT 
If no Load Shedding outputs are configured, there is no record to history and no scrren timer indication of the 
activity of this function.