When the BO CB close/open opens, there is 5 resp. 2 sec delay for the breaker to respond before a CB 
fail is detected. In such case, if CB OFF coil is used for opening the CB and CB fail occurs during 
opening the CB, the signal CB OFF coil is automatically extended until the breaker opening is detected 
(evaluated as CB status). 
 
•  2 sec when the CB is used for synchronizing 
•  5 sec in other cases 
 
 
 
  In case that CB fail is detected after switching the controller on (CB is closed), the CB OFF coil output is 
activated immediatelly. 
Remote Alarm Messaging 
It is possible to use up to five channels for Active Call, Email and SMS upon defined type of Alarm. It is 
possible to define protection type for all ENABLED channels to react. All the possibilities in the controller are: 
History record,  Alarm only, Warning, Mains  protect  and  Mains protect  with Reset. Find  more  information 
about alarm types in the chapter Protections and alarm management. 
Communication Types for Remote Alarm Messaging 
Below there all types of communication available for each Active Call channel. 
DATA-ANA:  This  option  sends  a  complete  archive  to  the  recipient's  PC  via  analog  modem.  An  analog 
modem must be connected either to one of controller COM ports or to one of I-LB modules connected to the 
controller via CAN2 bus. The channel address must contain complete telephone number of the recipient's 
PC where InteliMonitor is running in Active call receiving mode.   
DATA-GSM: This option sends a complete archive to the recipient's PC via GSM modem. A GSM modem 
with activated CSD data transfers must be connected either to one of controller COM ports or to one of I-LB 
modules connected to the controller via CAN2 bus. The channel address must contain complete telephone 
number of the recipient's PC where InteliMonitor is running in Active call receiving mode.   
DATA-ISDN: This option sends a complete archive to the recipient's PC via ISDN modem. An ISDN modem 
must  be  connected  either  to  one  of  controller  COM  ports  or  to  one  of  I-LB  modules  connected  to  the 
controller via CAN2 bus. The channel address must contain complete telephone number of the recipient's 
PC where InteliMonitor is running in Active call receiving mode.   
DATA-CDMA:  This  option  sends  a  complete  archive  to  the  recipient's  PC  via  CDMA  modem.  A  CDMA 
modem must be connected either to one of controller COM ports or to one of I-LB modules connected to the 
controller  via  CAN2  bus.  The  local  CDMA  network  must  allow  point-to-point  data  transfers.  The  channel 
address  must  contain  complete  telephone number  of the  recipient's  PC  where  InteliMonitor  is  running  in 
Active call receiving mode.   
SMS-GSM: This option sends a short text message (SMS) containing the actual Alarmlist contents to the 
recipient's  mobile  phone  via  the  GSM  modem.  The  channel  address  must  contain  complete  telephone 
number of the recipient's mobile phone.