History Related functions 
History Records Adjustment 
It is possible to change History records content. Each record contains date, time and cause of the record as 
obligatory columns. The rest of columns are configurable. 
The history record structure has two parts. The upper part is so-called fast and is written into the history 
memory immediately in the moment when the written event occurs. The rest of the record may be written 
with a delay max. 100ms. The fast part is intended for fast changing values as e.g. currents, voltages or 
power. The parts are separated by a line in the record content list. 
 
 
 
1.  Values selection tree  
2.  Buttons for adding/removing values into/from the record structure  
3.  Buttons for ordering of the values in the record structure  
4.  Fast history separator. The fast part is located above the separator  
5.  Estimated number of records depending on record size  
6.  Record capacity usage indicator  
NOTE: 
Values that are displayed in green color are recomended to be placed in the fast part. 
If the checkbox Add modules to history automatically.. in the Modules tab is checked then all values of a 
module are automatically added into the history record when the module is inserted into the configuration. 
Time Stamp function 
The  controller  allows  user  to  define  when  the  history  records  are  written  even  though  there  is  no  other 
reason for history record (so called Time Stamp). 
It is  possible to  disable  time  stamping function  (for  example  when  time  stamping is not  needed  and  just 
floods the history). It may be conditioned by activation of logical Binary Input function (TIME STAMP ACT) or it 
may be enabled always. 
Period of time stamping may be adjusted from 1 to 240 minutes. 
NOTE: 
Beware of History flooding by to many Time Stamps (vital information may be overwritten).