IGS-NT-BC, SW Version 1.2.0,   ©ComAp – January 2019                                     
IGS-NT-BC-1.2.0 Reference Guide.PDF 
 
The timer is activated every "x-th" day. The day period "x" is adjustable. Weekends can 
be excluded. E.g. the timer can be adjusted to every 2nd day excluding saturdays and 
sundays. 
The timer is activated every "x-th" week on selected weekdays. The week period "x" is 
adjustable. E.g. the timer can be adjusted to every 2nd week on monday and friday. 
The timer is activated every "x-th" month on the selected day. The requested day can 
be selected either as "y-th" day in the month or as "y-th" weekday in the month. E.g. the 
timer can be adjusted to every 1st month on 1st tuesday. 
 
The mode of each timer channel is adjusted by an assigned setpoint. The setpoints are located int the Timer 
settings group and can be adjusted via InteliMonitor and GenConfig. 
 
 
Figure: Principial scheme of one block containing 4 timers 
 
EXAMPLE: 
Below is an example how to use the timers for periodic tests of the gen-set performed every sunday with 
duration of 30 minutes and also for scheduled transfer of the load before expected mains failure announced 
by the local electricity distribution company to 1.5.2010 from 01:00 to 04:00. 
1.  The  output TIMERACT 1-4 is  configured  internally  in  GenConfig  (LBI  tab)  to  the  logical  binary 
inputs REMOTE TEST and TEST ON LOAD. 
2.  The setpoint Timer settings:TimerChannel 1 is adjusted to "repeated" mode, "weekly" period, only 
sundays, starting date/time next sunday at 0:00, timer duration 0:30 min. 
 
3.  The setpoint Timer settings:TimerChannel 2 is adjusted to "once" mode, starting date/time 1.5.2010 
at 01:00, timer duration 3:00 hrs.