IGS-NT-BC, SW Version 1.2.0,   ©ComAp – January 2019                                     
IGS-NT-BC-1.2.0 Reference Guide.PDF 
 
 
Analog input: Cold temp 4 
If there is an additional terminal board between a thermocouple and the IS-AIN8 
module and there is a significant temperature difference between this terminal 
board and the module, it is necessary to measure the temperature at this terminal 
board and use this temperature for the thermocouple compensation instead of the 
internal temperature of the module. 
This analog input is intended for measuement of this thermocouple compensation 
temperature for the IS-AIN8 module with index #4. 
NOTE:  
Thermocouples without internal compensation "Thermo(nc)..." must be used for 
this case. 
 
Table of binary output functions 
Binary output: Alarm 
The output is closed if there is at least one unconfirmed alarm in the alarm list. 
NOTE:  
Some alarm types as e.g. Off load, History record, Low power, Mains protection do 
not require confirmation, they disappear from the alarm list automatically when the 
alarm condition disappears. That means the Alarm output is not activated by 
alarms of these types.