IGS-NT-BC, SW Version 1.2.0,   ©ComAp – January 2019                                     
IGS-NT-BC-1.2.0 Reference Guide.PDF 
 
Add or Remove Custom sensor curve
General type of sensor
Custom curve name
Resolution of 
converted value
Add or Remove points from the curve
Order values from lowest to highest
Open curve points from file or save 
current curve to file
Curve preview (no preview is 
displayed if values or their order is 
not valid)
 
Figure: User Sensor definition 
Languages and Translator tool in GenConfig 
For detailed description of Languages and Translator tool please refer to GenConfig interactive help (press 
F1 when in corresponding tab or open Help -> GenConfig Help). 
Power Formats 
IGS-NT family allows user to choose from several Power Formats that affect dimensions in which values and 
some  setpoints  are  interpreted  or  adjusted.  Power  formats  may  be  changed  in  Miscellaneous  tab  in 
GenConfig. There are following Power Formats available: 
•  1 kW kVAr kVA kX V 
•  0,1 kW kVAr kVA kX V 
•  0,01 MW MVAr MVA MX kV 
•  0,01 MW MVAr MVA MX V 
NOTE:    
Range of some setpoints and values is changed significantly when different Power Formats are selected.
   
Last Power Format is designed to be used in combined Power/High Voltage and Low Voltage instalations. 
High voltage is then interpreted in Volts (e.g. 33256V instead of 33kV). 
Last two Power Formats can be used in combination on one CAN bus. 
System Start/Stop 
For proper function of the system, System start and stop signal needs to be used properly. Below there is 
scheme that shows how to use the Binary Output SYS START/STOP in the system using just CAN wiring (no 
physical wiring is needed to share the starting and stoping signal into all controllers in the system).