EasyManuals Logo

ComAp IG-NTC-BB Reference Guide

ComAp IG-NTC-BB
361 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #340 background imageLoading...
Page #340 background image
IGS-NT Combi, SW Version 3.0, ©ComAp – May 2013
IGS-NT-Combi-3.0 Reference Guide.PDF
340
Binary output: Soft unld
Related FW
3.0
Description
The output is closed while the gen-set is beeing unloaded before opening GCB.
Binary output: Cooling
Related FW
3.0
Description
The output is closed during the Cooling phase, which takes place after GCB has
been opened before the engine is stopped.
Binary output: Stopping
Related FW
3.0
Description
The output closes when the command to stop the engine has been issued, i.e. the
output Fuel Solenoid has been deactivated. It opens when the engine is fully
stopped. The output also closes if the engine begins to rotate spontaneously.
This output is closed for the whole time of the stopping sequence (regardless of
the repeated opening of the Stop solenoid). It is deactivated immediately when the
engine is considered stopped.
Binary output: Cranking
Related FW
3.0
Description
The output is closed while the engine is cranking. See the following diagrams for
differencies between outputs CrankProcedure, Cranking and Starter. The diagrams
show situation for gas engine and two crank attempts.
CRANKING OUTPUTS BEHAVIOR - SUCCESSFUL START
CRANKING OUTPUTS BEHAVIOR - UNSUCCESSFUL START

Table of Contents

Other manuals for ComAp IG-NTC-BB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp IG-NTC-BB and is the answer not in the manual?

ComAp IG-NTC-BB Specifications

General IconGeneral
BrandComAp
ModelIG-NTC-BB
CategoryController
LanguageEnglish

Related product manuals