EasyManua.ls Logo

ComAp InteliGen NT

ComAp InteliGen NT
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
InteliGen
NT
, InteliSys
NT
, InteliMains
NT
Troubleshooting Guide,
SW version IGS-NT-3.1.0, IM-NT-3.1.0, ©ComAp August 2018 32
IGS-NT Troubleshooting Guide.pdf
IGS-NT Alarm/History
record
Alarm/
History
Appeara
nce
Description
NotReady state is shown on the controller screen and the
message appears in the Alarm list. As soon as input is
deactivated, engine start is enabled again.
Wrn CylTemp1-32
A+H
Warning protection on AI Cylinder temperature 1-32 is
active. Check corresponding setpoints in the Engine
protect group.
Wrn MCB fail
A+H
MCB failure was detected.
See Circuit breakers operation sequence, GCB/MCB fail
detection chapter in IGS-NT-x.y-Reference Guide.
Stp GCB fail
A+H
GCB failure was detected.
See Circuit breakers operation sequence, GCB/MCB fail
detection chapter in IGS-NT-x.y-Reference Guide.
Wrn BTB fail
A+H
BTB failure was detected.
See Circuit breakers operation sequence, GCB/MCB fail
detection chapter in IGS-NT-x.y-Reference Guide. It
applies to BTB breaker too.
Wrn MGCB fail
MGCB failure was detected.
See Circuit breakers operation sequence, GCB/MCB fail
detection chapter in IGS-NT-x.y-Reference Guide. It
applies to MGCB breaker too.
Sd Oil press B
A+H
Engine shut-down was activated by binary input with “Oil
press” function (see LBI card in GenConfig for information
about source signal for this function).
Wrn RSync fail
A+H
Reverse synchronization failure indication, genset or group
of gensets was not synchronized to mains within
Sync/Load ctrl:Sync timeout time.
Check setting of setpoints in the Sync/Load ctrl and
Volt/PF ctrl groups. Frequency regulation loop, Angle
regulation loop and Voltage regulation loop are active
during synchronisation and you may need to adjust their
setting.
Actual state of synchronization is visible on the controller
measurement screen with synchroscope where speed and
voltage regulator's outputs, slip frequency and generator
and mains voltages can be observed during the
synchronization process.
Stp Sync fail
A+H
Synchronization failure indication (alarm Sync timeout is
active), gen-set or group of gensets was not synchronized
to mains/bus within Sync/Load ctrl:Sync timeout time.
Check setting of setpoints in the Sync/Load ctrl and
Volt/PF ctrl groups. Frequency regulation loop, Angle
regulation loop and Voltage regulation loop are active
during synchronisation and you may need to adjust their
setting.
Actual state of synchronization is visible on the controller
measurement screen with synchroscope where speed and
voltage regulators' outputs, slip frequency and generator
and mains/bus voltages can be observed during the
synchronization process.
Wrn Sync fail
A+H
Synchronization failure indication (alarm Sync timeout is
active), gen-set or group of gensets was not synchronized
to mains/bus within Sync/Load ctrl:Sync timeout time.
Check setting of setpoints in the Sync/Load ctrl and
Volt/PF ctrl groups. Frequency regulation loop, Angle
regulation loop and Voltage regulation loop are active

Table of Contents

Other manuals for ComAp InteliGen NT

Related product manuals