Page #141 background imageLoading...
Page #141 background image
IGS-NT Communication Guide
141
Bit 6-7 ................. Protection #1 Sensor failure
Value Meaning
0 Sensor failure not active
1 Sensor failure active, confirmed
2 Sensor failure previously active, not confirmed yet
3 Sensor failure active, not confirmed yet
Bit 8-10 ................. Protection #2 Level 1
Value Meaning
0 Level 1 inactive
2 Level 1 active, confirmed
3 Level 1 active, blocked
4 Level 1 previously active, not confirmed yet
6 Level 1 active, not confirmed yet
7 Level 1 active, not confirmed yet, blocked
Bit 11-13 ................. Protection #2 Level 2
Value Meaning
0 Level 2 inactive
2 Level 2 active, confirmed
3 Level 2 active, blocked
4 Level 2 previously active, not confirmed yet
6 Level 2 active, not confirmed yet
7 Level 2 active, not confirmed yet, blocked
Bit 14-15 ................. Protection #2 Sensor failure
Value Meaning
0 Sensor failure not active
1 Sensor failure active, confirmed
2 Sensor failure previously active, not confirmed yet
3 Sensor failure active, not confirmed yet

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliGen NTC BaseBox and is the answer not in the manual?

ComAp InteliGen NTC BaseBox Specifications

General IconGeneral
BrandComAp
ModelInteliGen NTC BaseBox
CategoryController
LanguageEnglish

Related product manuals