IGS-NT Communication Guide
151
MSB1
(*)
LSB1
(*)
MSB2
(*)
LSB2
(*)
Meaning
235 0 0 8
This error is reported by iG-MU module (Modem Bridge) in the case of a
connection failure between the module and the addressed controller. The
terminal can evaluate this error as a communication timeout with the
controller.
234 0 0 8 Write cannot be performed periphery not responding.
233 0 0 8 Write cannot be performed setpoint nonexistent in any periphery.
232 0 0 8 Bad access code for communication from a remote terminal.
231 0 0 8
Invalid controller address: value out of range 1 to 32 or already used. This
error is a reaction on communication object. Object 24537 write.
230 0 0 8 Error in definition for communication oscilloscope objects.
229 0 0 8
Undefined action. A reaction on communication object. Object 24521
write.
228 0 0 8
Action (although defined) cannot be performed. A reaction on
communication object. Object 24521 write.
227 0 0 8 Written object value is not acceptable.
226 0 0 8 No more free slots.
225 0 0 8 No connection.
224 0 0 8 Locked, block reading is active.
223 0 0 8 Locked, commanding is active.
222 0 0 8 Locked, the history reading is active.
221 0 0 8 Locked, the programming is active.
220 0 0 8 Communication error.
219 0 0 8 Request for data.
218 0 0 8 Request for SMS.
217 0 0 8 Request for email.
216 0 0 8 Request for mobile email.
215 0 0 8 Request for - fax.
214 0 0 8 Wrong access code, the connection must be terminated.
213 0 0 8 Reserved for HW key.
212 0 0 8 Reserved for DENOX.
211 0 0 8 Unsufficient access rights.
210 0 0 8 The request can be submitted only by the administrator (User 0).
209 0 0 8 The administrator has entered a wrong user identification number.
208 0 0 8 Not possible to write, the communication object has forced value.
207 0 0 8 The administrator requests an unsupported operation.
206 0 0 8 Selected communication mode doesn’t allow required interface.
205 0 0 8 Selected interface doesn’t allow required communication mode.
204 0 0 8
HW data flow control for modem communication. Sending as answer to
request to read 24437 communication object.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliGen NTC BaseBox and is the answer not in the manual?

ComAp InteliGen NTC BaseBox Specifications

General IconGeneral
BrandComAp
ModelInteliGen NTC BaseBox
CategoryController
LanguageEnglish

Related product manuals