Setpoint group Engine settings Related FW 1.9.0
Range [units] -20,0 .. 80,0 [°C]
Default value 0,0 °C Alternative config NO
Step 0,1 °C
Comm object 15716 Related applications MRS. AMF
Config level Advanced
Setpoint visibility
Only when LBO CHOKE (PAGE 567) is configured and setpoint Choke Function (page
193) = Temp Based.
Description
This setpoint adjust the base temperature for Choke function. When temperature will be higher than this
setpoint, Choke Time will be always 0. When temperature will be lower than this setpoint, Choke Time will
be calculated by curve adjusted via setpoint Choke Increment (page 195). When setpoint Choke
Function (page 193) is set to Fixed Time value, setpoint Choke Start Temp has no effect.
Choke Start Temp