InteliLite Global Guide
195
Setpoint group Engine settings Related FW 1.9.0
Range [units] 0,00 .. 20,00 [s/°C]
Default value 0,00 s/°C Alternative config NO
Step 0,01 s/°C
Comm object 15715 Related applications MRS. AMF
Config level Advanced
Setpoint visibility
Only when LBO CHOKE (PAGE 567) is configured and setpoint Choke Function
(page 193) = Temp Based.
Description
This setpoint adjust the maximal time of activation of binary output CHOKE (PAGE 567). Calculated time
depends on engine (coolant) temperature. Setpoint adjust curve which is used for calculating actual Choke
Time. When setpoint Choke Function (page 193) is set to Fixed Time value, setpoint Choke Increment has
no effect.
Note: If setpoint Choke Lead (page 197) is set to nonzero value, total time the CHOKE output is
activated still matches calculated value (based on actual temperature and setpoints Choke Increment
and Choke Start Temp (page 194)) This mean that adjusted parameters should ensure that calculated
Choke Time will be longer than Choke Leadto ensure expected Choke behavior.
Choke Increment
6 back to List of setpoints

Table of Contents

Other manuals for ComAp InteliLite MRS16

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite MRS16 and is the answer not in the manual?

ComAp InteliLite MRS16 Specifications

General IconGeneral
BrandComAp
ModelInteliLite MRS16
CategoryController
LanguageEnglish

Related product manuals