InteliLite Global Guide
207
Subgroup: Engine Protections
Setpoint group Engine settings Related FW 1.9.0
Range [units] Underspeed Sd (page 207) .. 200 [%]
Default value 115% Alternative config NO
Step 1 % of Nominal RPM (page 181)
Comm object 8263 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Threshold for over speed protection. Relative to the nominal speed.
Overspeed Sd
6 back to List of setpoints
Setpoint group Engine settings Related FW 1.9.0
Range [units] 0 .. Overspeed Sd (page 207) [%]
Default value 25% Alternative config NO
Step 1 % of Nominal RPM (page 181)
Comm object 8260 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Threshold for underspeed protection. Relative to the nominal speed.
Underspeed Sd
6 back to List of setpoints
Setpoint group Engine settings Related FW 1.9.0
Range [units] 0 .. 50 [%]
Default value 20% Alternative config NO
Step 1 % of Nominal RPM (page 181)
Comm object 14107 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
This setpoint rise the upper limit of overspeed protection for the time which is defined in setpoint Overspeed
Overshot Period (page 208). In this time the upper limit of protection is Overspeed Sd (page 207) +
Overspeed Overshoot.
Overspeed Overshot
6 back to List of setpoints

Table of Contents

Other manuals for ComAp InteliLite MRS16

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite MRS16 and is the answer not in the manual?

ComAp InteliLite MRS16 Specifications

General IconGeneral
BrandComAp
ModelInteliLite MRS16
CategoryController
LanguageEnglish

Related product manuals