InteliLite Global Guide
236
Setpoint group Protections Related FW 1.9.0
Range [units] Enabled / Disabled / By LBI[-]
Default value Enabled Alternative config NO
Step [-]
Comm object 15666 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
This setpoint adjusts the behavior of generator IDMT Overcurrent protection.
Enabled:
Protection is enabled. Behavior of protection is adjusted via setpoint IDMT
Overcurrent Delay (page 229).
Disabled: Protection is disabled.
By LBI: Protection is enabled or disabled by the state of LBI PROTECTION ENABLE (PAGE 534).
IDMT Overcurrent Protection
6 back to List of setpoints
Setpoint group Protections Related FW 1.9.0
Range [units] Enabled / Disabled / By LBI[-]
Default value Enabled Alternative config NO
Step [-]
Comm object 15667 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
This setpoint adjusts the behavior of generator Current Unbalance protection.
Enabled:
Protection is enabled. Behavior of protection is adjusted via setpoints Current
Unbalance BOC (page 230) and Current Unbalance BOC Delay (page 230).
Disabled: Protection is disabled.
By LBI: Protection is enabled or disabled by the state of LBI PROTECTION ENABLE (PAGE 534).
Current Unbalance Protection
6 back to List of setpoints

Table of Contents

Other manuals for ComAp InteliLite MRS16

Questions and Answers: