InteliLite Global Guide
237
Subgroup: Voltage Protection
Setpoint group Protections Related FW 1.9.0
Range [units] Enabled / Disabled / By LBI [-]
Default value Enabled Alternative config NO
Step [-]
Comm object 15668 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
This setpoint adjusts the behavior of generator Generator <> Voltage protection. GCBclosing is blocked, if
the protection is disabled!
Enabled:
Protection is enabled. Behavior of protection is adjusted via setpoints Generator
Overvoltage Sd (page 230), Generator Overvoltage Wrn (page 231), Generator
Undervoltage BOC (page 231), Generator Undervoltage Wrn (page 232) and
Generator <> Voltage Delay (page 232).
Disabled: Protection is disabled.
By LBI: Protection is enabled or disabled by the state of LBI PROTECTION ENABLE (PAGE 534).
Generator <> Voltage Protection
6 back to List of setpoints
Setpoint group Protections Related FW 1.9.0
Range [units] Enabled / Disabled / By LBI [-]
Default value Enabled Alternative config NO
Step [-]
Comm object 15669 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
This setpoint adjusts the behavior of generator Voltage Unbalance protection.
Enabled:
Protection is enabled. Behavior of protection is adjusted via setpoints Voltage
Unbalance BOC (page 232) and Voltage Unbalance BOC Delay (page 233).
Disabled: Protection is disabled.
By LBI: Protection is enabled or disabled by the state of LBI PROTECTION ENABLE (PAGE 534).
Voltage Unbalance Protection
6 back to List of setpoints