When the Rental Timer 2 (page 319) elapsed during engine run the gen-set will not stop immediately. The
adjustable Rental Timer BOC (page 321) timer will start in this moment. The engine will be cooled and
stopped when the Rental Timer BOC (page 321) time elapsed.
Image 8.62 Rental Timer 2
The Running Hours Overrun counter will start increment when the engine is continue running after the Rental
Timer 2 (page 319) elapsed.
Note: There is no priority between Rental Timer 1 and Rental Timer 2. The sooner timer will activated the
Rental Timer BOC (page 321) protection.