Setpoint group Scheduler Related FW 1.9.0
Range [units] Disabled / 01/01/2015 .. Rental Timer 2 (page 319) [DD/MM/YYYY]
Default value 01/01/2015 Alternative config NO
Step 1 day
Comm object 14368 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Conditioned by the setpoint Rental Timer 2 (page 319)
Description
Alarm Wrn Rental Timer 2 (page 663) comes up xx days before the Rental Timer 2 (page 319). Days are
adjusted by this setpoint.
Image 8.63 Rental Timer 2 Wrn
Rental Timer 2 Wrn
6 back to List of setpoints
Setpoint group Scheduler Related FW 1.9.0
Range [units] Disabled / 1 .. 210 [h]
Default value 24 h Alternative config NO
Step 1 h
Comm object 14334 Related applications AMF, MRS
Config level Advanced
Setpoint visibility
Conditioned by the setpoints Rental Timer 1 (page 317) and Rental Timer 2 (page
319)
Description
This timer will start after Rental Timer 1 (page 317) or Rental Timer 2 (page 319) elapsed in case that the
engine is still running. When this timer elapsed the engine is cooled and stopped.
Rental Timer BOC
6 back to List of setpoints