IGS-NT Combi, SW Version 3.0, ©ComAp May 2013
IGS-NT-Combi-3.0 Reference Guide.PDF
41
DATA-ANA: This option sends a complete archive to the recipient's PC via analog modem. An analog
modem must be connected either to one of controller COM ports or to one of I-LB modules connected to the
controller via CAN2 bus. The channel address must contain complete telephone number of the recipient's
PC where InteliMonitor is running in Active call receiving mode.
DATA-GSM: This option sends a complete archive to the recipient's PC via GSM modem. A GSM modem
with activated CSD data transfers must be connected either to one of controller COM ports or to one of I-LB
modules connected to the controller via CAN2 bus. The channel address must contain complete telephone
number of the recipient's PC where InteliMonitor is running in Active call receiving mode.
DATA-ISDN: This option sends a complete archive to the recipient's PC via ISDN modem. An ISDN modem
must be connected either to one of controller COM ports or to one of I-LB modules connected to the
controller via CAN2 bus. The channel address must contain complete telephone number of the recipient's
PC where InteliMonitor is running in Active call receiving mode.
DATA-CDMA: This option sends a complete archive to the recipient's PC via CDMA modem. A CDMA
modem must be connected either to one of controller COM ports or to one of I-LB modules connected to the
controller via CAN2 bus. The local CDMA network must allow point-to-point data transfers. The channel
address must contain complete telephone number of the recipient's PC where InteliMonitor is running in
Active call receiving mode.
SMS-GSM: This option sends a short text message (SMS) containing the actual Alarmlist contents to the
recipient's mobile phone via the GSM modem. The channel address must contain complete telephone
number of the recipient's mobile phone.
SMS-CDMA: This option sends a short text message (SMS) containing the actual Alarmlist contents to the
recipient's mobile phone via the CDMA modem. The channel address must contain complete telephone
number of the recipient's mobile phone.
IB-E-MAIL: This option sends an e-mail containing the actual Alarmlist contents and latest 20 history records
(only date, time, reason) to the recipient's mailbox via the IB-COM module or IG-IB module. The channel
address must contain valid e-mail address of the recipient.
NOTE:
The SMTP settings (SMTP authent,SMTP user name, SMTP password, SMTP address, Contr mailbox) must
be properly adjusted for sending e-mails.
Example of setting
There is an example of setting of Remote Alarm Messaging. In this case active calls we be triggered on
Mains protect and Mains protect with Reset alarms. Message is sent via email to
emailAddress@domain.com (Channel 1 available for NTC controller or with any controller with connected
IB-NT or I-LB+), archive is sent via ISDN modem to the number +111222333444 (Channel 2) and SMS is
sent to the number +999111333555 (Channel 3).
It is also possible to adjust number of attempts that controller performs in case of not successful Active Call
Comms settings:ActCallAttempt. The language of messages can be changed
Comms settings:Acall+SMS lang (use Translator and Languages tabs in GenConfig to adjust languages).
Up to five channels can be used.

Table of Contents

Other manuals for ComAp IS-NTC-BB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp IS-NTC-BB and is the answer not in the manual?

ComAp IS-NTC-BB Specifications

General IconGeneral
BrandComAp
ModelIS-NTC-BB
CategoryController
LanguageEnglish

Related product manuals