MainsPro G99TT 1.0.0 Global Guide
49
Setting
Setpoint
group
Setpointname Adjustable Value Step Unit
Underfrequency
delay 2
Overfrequency
hysteresis
f<> Rstf>, Rstf>> No 100 0.1 [%]
Underfrequency
hysteresis
f<> Rstf<, Rstf<< No 100 0.1 [%]
Vector shift limit LOM Vs Lim No 0 (OFF) 1 [°]
ROCOF limit LOM ROCOF No 1 0.01 [Hz/s]
ROCOF filter LOM ROCOF Filt No 9 1 [-]
ROCOF delay LOM ROCOF Del No 0.5 0.01 [s]
Delay of Vector
shift
and ROCOF
evaluation after
measured voltage
connection
LOM LOMInitDel No 3 1 [s]
Vector shift and
ROCOF
signalization time
(TRIP duration)
LOM LOM Trp Del No 3 1 [s]
Measurement
range
Basic Uin All the time 230 - [V]
Measured system Basic System All the time 3ph - -
Display timeout Basic DispT All the time 0 1 [min]
Automatic Fault
Reset enabling
Basic Auto FR All the time ENABLED - -
Automatic Fault
Reset timer
Basic AutoFRDel All the time 20 1 [s]
TRIP at the unit
startup
Basic Start Trip All the time DISABLED - -
Common impulse
length
Basic Imp Len All the time 3 1 [s]
Back-up Trip
Output Delay
Basic Bak Trp Del All the time 0.5 0.1 [s]
Enabling the
external trip binary
switch
Basic Ext All the time ENABLED - -
Enabling the fault
Reset binary
switch
Basic F.R. All the time DISABLED - -