Mains pro 1.6.1 Global Guide
48
Setting
Setpoint
group
Setpointname Value Step Unit
Undervoltage limit 2
Undervoltage delay 2
V<>
V<>
V<<
V<< Del
0
0.50
1
0.01
[V]
[s]
10 minutes floating average
overvoltage*
V<> Avg V> 0 (OFF) 1 [V]
Overvoltage hysteresis V<> RstV>,RstV>> 100 1 [%]
Undervoltage hysteresis V<> RstV<,RstV<< 100 1 [%]
Voltage asymmetry limit
Negative sequence overvoltage limit
Positive sequence undervoltage limit
Common delay of all voltage asymmetry
protections
dU
dU
dU
dU
V unb
V> neg
V< pos
dU Del
0.0 (OFF)
0.0 (OFF)
0.0 (OFF)
2.50
0.1
0.1
0.1
0.01
[%]
[%]
[%]
[s]
Overfrequency limit 1
Overfrequency delay 1
f<>
f<>
f>
f> Del
0
0
0.1
0.01
[Hz]
[s]
Overfrequency limit 2
Overfrequency delay 2
f<>
f<>
f>>
f>> Del
52.00
0.50
0.1
0.01
[Hz]
[s]
Underfrequency limit 1
Underfrequency delay 1
f<>
f<>
f<
f< Del
47.50
20.00
0.1
0.01
[Hz]
[s]
Underfrequency limit 2
Underfrequency delay 2
f<>
f<>
f<<
f<< Del
47.00
0.50
0.1
0.01
[Hz]
[s]
Overfrequency hysteresis f<> Rstf>,Rstf>> 100 0.1 [%]
Underfrequency hysteresis f<> Rstf<,Rstf<< 100 0.1 [%]
Vector shift limit
ROCOF limit
ROCOF filter
ROCOF delay
Vector shift and ROCOF evaluation delay
LOM
LOM
LOM
LOM
LOM
Vs Lim
ROCOF
ROCOF Filt
ROCOF Del
LOM Init Del
0
1
9
0.5
3
1
0.01
1
0.01
1
[°]
[Hz/s]
[-]
[s]
[s]
Vector shift and ROCOF signalization time
(TRIP duration)
LOM LOM Trp Del 3 1 [s]
Measurement range Basic Uin 230 - [V]
Measured system Basic System 3ph - -
Display timeout Basic DispT 0 1 [min]
Automatic Fault Reset enabling Basic Auto FR ENABLED - -
Automatic Fault Reset timer Basic Auto FR Del ˃20 1 [s]
TRIP at the unit startup Basic Start Trip DISABLED - -
Common impulse length Basic Imp Len 3 1 [s]
Back-up Trip Output Delay Basic Bak Trp Del 0.5 0.1 [s]
Enabling the external trip binary switch Basic Ext ENABLED - -