Mains pro 1.6.1 Global Guide
49
Setting
Setpoint
group
Setpointname Value Step Unit
Enabling the fault Reset binary switch Basic F.R. DISABLED - -
Enabling the Alt settings binary switch Basic Alt ENABLED - -
Enabling the blocking binary switch Basic Dis DISABLED - -
Function of 1
st
relay output f(RE) f(RE1) !CommTrpPer - -
Function of 2
nd
relay output f(RE) f(RE2) CommTrpImp - -
Function of 3
rd
relay output f(RE) f(RE3) BakTrpImp - -
Function of 4
th
relay output f(RE) f(RE4) !InternFail - -
Function of 5
th
relay output f(RE) f(RE5) TrpEndImp - -
Note: Please note, that the indicated setting is adjusted for "Star" connection of the measured voltage, i.e. ph-
to-N voltage measurement. In case of using "Delta" connection, the appropriate change of the setpoints is
necessary. Please refer to the MainsPro Installation and Operation Guide for the wiring explanation and to the
MainsPro Reference Guide for information about the setpoints adjustment.
ComAp states that the mentioned setting is guaranteed for all MainsPro units, SW version 1.5, upon shipment
of a new unit, if no other setting is explicitly requested. In case of need, the factory default settings can be
provided by the following procedure:
1. Enter the init screen, by pushing the ENTER and ESCat the same time.
2. Press ← and ↓ to enter the Factory default activation screen:
3. Using ← and → do your selection. By selecting YES, you will return all previously done setting to the default
values. Please note that by this selection, you will lose all setting done prior to this operation!
Press ENTER to confirm your selection.
4. By selecting NO and pressing ENTER or by pressing ESC, return to the measurement screens with no
change.
6 back to Technical data