MainsPro, SW version 1.4, ©ComAp – January 2013 
MainsPro Installation and Operation Guide 
Connection with voltage transformers 
 
MainsPro allows connecting HV or other measurement transformers with secondary rated voltage 
100V. Provide the "Star" or "Delta" arrangement on the primary windings of the transformers and 
connect the secondary 100 V to the MainsPro measurement inputs. Setpoint Basic: Uin is to be set to 
120V. This setting provides the guaranteed measurement accuracy for the 100V inputs with over-
range to 120V * 130% = 156 VAC. 
 
Note: 
It is recommended to use “Delta” arrangement on the HV side to avoid nuisance tripping caused by 
phase voltage unbalance. 
 
Single-phase connection 
MainsPro provides support for single-phase applications. Use the U
A
 terminals to connect the 
measured voltage to the unit and set the setpoint Basic: System to 1ph. Use the same setting of rated 
voltage selection as mentioned above. 
 
 
 
Power supply 
MainsPro provides set of 3 terminals for the purpose of dual power supply range: 
  8 - 40 VDC: use the terminals + and N/- 
  85 - 265 VAC / 110-370 VDC: use the terminals L/+and N/-