MainsPro, SW version 1.4, ©ComAp January 2013
MainsPro Installation and Operation Guide
1-14
3. By button or , enter the setpoint group, by button , move one level up in the
setpoint tree. The setpoints are displayed in the cycling order, i.e. from the last setpoint by
button , the cursor moves to the first one and vice versa.
4. If standing on a setpoint, the setpoint change screen opens by pressing or . In the
screen, see the setpoint limits at the lowest row of the screen.
5. The change is done by orders, starting form the least important digit. Use the buttons and
to move between the digits. Use the buttons and to edit the digit. Please note,
that the value is not limited by the parameters limits during editing, but if an out-of-limits value
is set-up, it will not be allowed to store in the unit memory (the change may not be confirmed).
6. After the setpoint change is done, press to confirm the set value, or to leave the
setpoint change screen without saving the changes.
Please note: the unit allows mechanical sealing of the setpoints by the black switch in left-bottom
corner of the unit. If locked, the icon of closed padlock will appear on the position of setpoint
change and the setpoints may not be changed. Also, the padlock icon will be seen on the
“homepage” measurement screen. Once the setpoint change screen is entered and afterwards the
sealing position is changed, the padlock indication is not changed, but the internal lock is applied
immediately.
Reset operation time
1. Enter the init screen, by pushing the and at the same time.
2. Press to enter the Reset Oper.Time? screen:
3. Using and do your selection. By selecting YES, Operation Time" timer will be reset,
and the last five events will be deleted. Press to confirm your selection.
4. By selecting NO and pressing or by pressing , return to the measurement screens with
no change.
Reset trip counters
1. Enter the init screen, by pushing the and at the same time.
2. Press to enter the Clear Statistics dialog screen:
3. Using and do your selection. By selecting YES, all trip counters will be reset. Press
to confirm your selection.
4. By selecting NO and pressing or by pressing , return to the measurement screens with
no change.