MainsPro, SW version 1.4, ©ComAp January 2013
MainsPro Reference Guide
3-20
Statement of the factory default setting
of MainsPro unit
NOTE:
The following default setting is available from version 1.4. For older versions, different factory default
setting was applied.
Setting
Setpoint
group
Setpoint name
Value
Step
Unit
Overvoltage limit 1
*)
Overvoltage delay 1
V<>
V<>
V>
V> Del
460
0,20
1
0,01
[V]
[s]
Overvoltage limit 2
Overvoltage delay 2
V<>
V<>
V>>
V>> Del
0 (OFF)
2,50
1
0,01
[V]
[s]
Undervoltage limit 1
*)
Undervoltage delay 1
V<>
V<>
V<
V< Del
340
0,40
1
0,01
[V]
[s]
Undervoltage limit 2
Undervoltage delay 2
V<>
V<>
V<<
V<< Del
160
0,20
1
0,01
[V]
[s]
10 minutes floating average overvoltage*
V<>
Avg V>
440
1
[V]
Voltage asymmetry limit
Negative sequence overvoltage limit
Positive sequence undervoltage limit
Common delay of all voltage asymmetry
protections
dU
dU
dU
dU
V unb
V> neg
V< pos
dU Del
0 (OFF)
0 (OFF)
0 (OFF)
2,50
1
1
1
0,01
[V]
[V]
[V]
[s]
Overfrequency limit 1
Overfrequency delay 1
f<>
f<>
f>
f> Del
51,5
1,00
0,1
0,01
[Hz]
[s]
Overfrequency limit 2
Overfrequency delay 2
f<>
f<>
f>>
f>> Del
0 (OFF)
0,10
0,1
0,01
[Hz]
[s]
Underfrequency limit 1
Underfrequency delay 1
f<>
f<>
f<
f< Del
47,5
4,00
0,1
0,01
[Hz]
[s]
Underfrequency limit 2
Underfrequency delay 2
f<>
f<>
f<<
f<< Del
0 (OFF)
0,10
0,1
0,01
[Hz]
[s]
Vector shift limit
ROCOF limit
ROCOF filter
Delay of Vector shift and ROCOF evaluation
after measured voltage connection
LOM
LOM
LOM
LOM
Vs Lim
ROCOF
ROCOF Filt
LOM Init Del
0 (OFF)
0 (OFF)
5
3
1
0,01
1
1
[°]
[Hz/s]
[-]
[s]