MainsPro, SW version 1.4, ©ComAp January 2013
MainsPro Reference Guide
3-21
Setting
Setpoint
group
Setpoint name
Value
Step
Unit
Vector shift and ROCOF signalization time
(TRIP duration)
LOM
LOM Trip Del
3
1
[s]
Measurement range
Basic
Uin
230/400V
-
-
Measured system
Basic
System
3ph
-
-
Display timeout
Basic
DispT
0
1
[min]
Automatic Fault Reset enabling
Basic
Auto FR
ENABLED
-
-
Automatic Fault Reset timer
Basic
Auto FR Del
0
1
[s]
TRIP at the unit startup
Basic
Start Trip
DISABLED
-
-
Common impulse length
Basic
Imp Len
3
1
[s]
Enabling the external trip binary switch
Basic
Ext
ENABLED
-
-
Enabling the fault Reset binary switch
Basic
F.R.
DISABLED
-
-
Enabling the Alt settings binary switch
Basic
Alt
ENABLED
-
-
Enabling the blocking binary switch
Basic
Dis
DISABLED
-
-
Function of 1
st
relay output
f(RE)
f(RE1)
!CommTrpPer
-
-
Function of 2
nd
relay output
f(RE)
f(RE2)
CommTrpImp
-
-
Function of 3
rd
relay output
f(RE)
f(RE3)
BakTrpImp
-
-
Function of 4
th
relay output
f(RE)
f(RE4)
!InternFail
-
-
Function of 5
th
relay output
f(RE)
f(RE5)
TrpEndImp
-
-
*) NOTE:
Please note, that the indicated setting is adjusted for "Star" connection of the measured voltage, i.e.
ph-to-N voltage measurement. In case of using "Delta" connection, the appropriate change of the
setpoints is necessary. Please refer to the MainsPro Installation and Operation Guide for the wiring
explanation and to the MainsPro Reference Guide for information about the setpoints adjustment.
ComAp states that the mentioned setting is guaranteed for all MainsPro units, SW version 1.4, upon
shipment of a new unit, if no other setting is explicitly requested. In case of need, the factory default
settings can be provided by the following procedure:
1. Enter the init screen, by pushing the and at the same time.
2. Press and to enter the Factory default activation screen:
3. Using and do your selection. By selecting YES, you will return all previously done
setting to the default values. Please note that by this selection, you will loose all setting
done prior to this operation! Press to confirm your selection.
4. By selecting NO and pressing or by pressing , return to the measurement screens with
no change.