MainsPro, SW version 1.4, ©ComAp – January 2013
MainsPro Installation and Operation Guide
Indication of LED LOM is immediate at detection of the particular protection stage (Vector shift
or ROCOF) and fault indication remains active for the period of time, set by the setpoint Basic:
Imp Len Del.
TRIP signalization is delayed according to the particular delay of the appropriate protective
stage.
Meaning of signalling LEDs
The unit has the appropriate outputs in TRIP position and the
unit is sensing a fault situation
The unit has the appropriate outputs in TRIP position, but the
unit is sensing fault-free situation. Fault reset is possible.
The unit has no output in TRIP position
Voltage of any phase is above threshold for 1st or 2nd stage
overvoltage
Voltage of any phase is under threshold for 1st or 2nd stage
undervoltage
Voltage unbalance (amplitude) is indicated.
If activated together with LED f and LOM, indicates incorrect
phase rotation
Negative sequence overvoltage or Positive sequence
undervoltage is indicated.
If activated together with LED f and LOM, indicates incorrect
polarity of one phase
All voltages are in fault-free state
10 minutes floating average overvoltage is detected
Over/under voltage protections are not enabled by setpoint
and no other voltage failure is sensed
Frequency as sensed on terminals Ua is above threshold for
1st or 2nd stage overfrequency
Frequency as sensed on terminals Ua is under threshold for
1st or 2nd stage underfrequency
Together with LED U and LOM, indicates incorrect phase
rotation
Together with LED U and LOM, indicates incorrect polarity of
one phase
Frequency, rotation and phases polarity are in fault-free state
Over/under frequency is protections are not enabled by
setpoint and no other indicated failure is sensed
Vector shift or ROCOF protection was indicated and Fault
reset was not yet done
Together with LED U and f, indicates incorrect phase rotation
Together with LED U and f, indicates incorrect polarity of one
phase
None of Vector shift or ROCOF failure is detected or neither
Vector shift nor ROCOF protections are not enabled by
setpoint and no other indicated failure is sensed
Indication of severe internal failure. Contact ComAp technical
support!