MainsPro, SW version 1.4, ©ComAp – January 2013 
MainsPro Installation and Operation Guide 
Binary switches status screen: 
 
- List of the assigned binary switches.  
Functions that are configured are displayed in the    
appropriate order.  
 Its status is displayed in brackets. 
Relay outputs 1-4 status screen: 
 
- Status of the first 4 MainsPro relay outputs.  
 Name in parenthesis marks the function assigned  
 by the setpoints in group f(RE). 
Relay output 5 status screen: 
 
- Status of the 5th MainsPro relay output.  
 Name in parenthesis marks the function assigned  
 by the setpoints in group f(RE). 
Trip counters and indication screen: 
 
 
 
-  Last Trip: indication of the latest event, which 
caused trip. See the following chapter for trip 
messages explanation. 
-  TripCnt: total counter of MainsPro trips since the 
MainsPro unit counters reset 
-  U: counter of overvoltage and undervoltage -related 
trips 
-  f: counter of overfrequency and underfrequency - 
related trips 
-  LOM: counter of Loss-of-Mains - related trips (Vector 
shift and ROCOF) 
-  Otr: counter of trips with other reason then the 
above mentioned: External trip, voltage asymmetry, 
phase sequence or inverse phase polarity 
-  Operation Time: time since MainsPro was powered 
up* 
-  Last Trip Time: time of the latest trip since MainsPro 
was powered-up 
Please note that the time information on the MainsPro 
unit is not measured by a calibrated RTC device and 
may serve for orientation purposes only. Find more in 
Technical data chapter. 
 - List of last five trips  - contains reason of the trip and time  
 since the unit was powered up 
*For case of power cut off, the time stamp is stored and after the unit is powered up again, the timer will start from 
the from following second after the last stored one.