21
LEVEL 1
↓ SET
Ptp
Set-point patterns (profile programs)
1
Range: 1 - for 1 pattern with 8 segments, 2 - for 2 patterns with 8 segments each,
0 - links 2 patterns together (16 segments)
↓ SET
SEG
Displays the current pattern segment
1_1
Range: 1_1 (1
st
pattern_1
st
segment) to 2_8, 1_0 means program stopped
↓ SET
tIMr
Program countdown timer - displays the rest segment time
0)00
Range: 0 to 99:59 (hours or minutes, depending on SET9.2)
↓ SET
SV_1
Set-point value at the end of segment 1
Range: LSPL to USPL
↓ SET
tM_1
Time duration of segment 1
0)00
Range: 0 to 99:59 (hours or minutes, depending on SET9.2)
↓ SET
OUt1
Output limit of segment 1
10)0
Range: 0 to 100% (100 - no limit, 0 - cancels the segment and ends the program)
…
SV_8
Set-point value at the end of segment 8
Range: LSPL to USPL
↓ SET
tM_8
Time duration of segment 8
0)00
Range: 0 to 99:59 (hours or minutes, depending on SET9.2)
↓ SET
Out8
Output limit of segment 8
10)0
Range: 0 to 100% (100 - no limit, 0 - cancels the segment and ends the program)
↓ SET
Returns to LEVEL 1