EasyManuals Logo

COMECO RT1800 User Manual

COMECO RT1800
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #6 background imageLoading...
Page #6 background image
6
Press SET to confirm the adjusted value and exit parameter value adjustment mode.
To display the next parameter in the row, press SET.
3.4. Controller programming
Automatic PID control parameter tuning (Auto-tune)
Before starting the Auto-tune function, ensure the controller is properly installed, the system is functional,
and the main parameters from levels 3 and 4 are already adjusted. The auto-tuning function automatically sets
the values of the following parameters: P1, i1, db1, GAP1, P2, i2, d2. The operator must set
manually the duration of the on/off output relay cycle CYt1, CYt2. For current output set to 0, for relay
output try with 10.
a) Set the parameter At to YES.
b) Set a temporary automatic decrease of the set point during auto tuning via the AtVL parameter.
With AtVL = 0, the tuning process will be performed around the set point. With AtVL = 5 °C
and set point SV = 200 °C, the auto-tuning will be performed around 195 °C (this avoids overheating
due to the process variable cycling during the auto-tuning process). If in doubt, set AtVL = 0.
c) Unsuccessful auto-tuning. Possible reasons are:
Too high AtVL value (if in doubt, set to 0).
Great system inertia. Set PID parameters manually.
3.4.1. Programming at LEVEL 1
Normally, the controller is at level 1 and displays the measured value. To view the next parameter
from this level, press SET.
95
PV Measured value
100
SV Set point
SET
OUtL
In manual mode: output value in percents from 0 to 100%
100
In auto mode scales down control output; it is recommended to keep the value = 100%
SET
At
Enable/disable auto-tuning
YES / nO See "Automatic PID control parameter tuning (Auto-tune)" above
SET
AL1
Alarm 1 limit
0
SET
AL2
Alarm 2 limit
0
SET
AL3
(
rAMP
)
Alarm 3 limit (Ramp slope)
0
SET
over again
! With OUtL = 0 during PID control, the output is switched off.
To achieve proper output operation in AUTO mode, set OUtL = 100.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the COMECO RT1800 and is the answer not in the manual?

COMECO RT1800 Specifications

General IconGeneral
BrandCOMECO
ModelRT1800
CategoryController
LanguageEnglish

Related product manuals