4. APPENDICES
4.1. Input type and range codes (inP1)
TYPE CODE RANGE
K1
0.0 ÷ 200.0
o
C
K2
0.0 ÷ 400.0
o
C
K3
0 ÷ 600
o
C
K
K4
0 ÷ 800
o
C
K5
0 ÷ 1000
o
C
K6
0 ÷ 1200
o
C
J1
0.0 ÷ 200.0
o
C
J2
0.0 ÷ 400.0
o
C
J3
0 ÷ 600
o
C
J
J4
0 ÷ 800
o
C
J5
0 ÷ 1000
o
C
J6
0 ÷ 1200
o
C
r1
0 ÷ 1600
o
C
R
r2
0 ÷ 1769
o
C
S1
0 ÷ 1600
o
C
S
S2
0 ÷ 1769
o
C
B
b1
0 ÷ 1820
o
C
E1
0 ÷ 800
o
C
E
E2
0 ÷ 1000
o
C
n1
0 ÷ 1200
o
C
N
n2
0 ÷ 1300
o
C
t1
-199.9 ÷ 400
o
C
T
t2
-199.9 ÷ 200
o
C
t3
0.0 ÷ 350.0
o
C
W1
0 ÷ 2000
o
C
W
W2
0 ÷ 2320
o
C
PL1
0 ÷ 1300
o
C
PLII
PL2
0 ÷ 1390
o
C
U1
-199.9 ÷ 600.0
o
C
U
U2
-199.9 ÷ 200.0
o
C
U3
0.0 ÷ 400.0
o
C
TYPE CODE RANGE
L1
0 ÷ 400
o
C
L
L2
0 ÷ 800
o
C
JP1
-199.9 ÷ 600.0
o
C
JP2
-199.9 ÷ 400.0
o
C
JIS
JP3
-199.9 ÷ 200.0
o
C
Pt100
JP4
0 ÷ 200
o
C
JP5
0 ÷ 400
o
C
JP6
0 ÷ 600
o
C
dP1
-199.9 ÷ 600.0
o
C
dP2
-199.9 ÷ 400.0
o
C
DIN
dP3
-199.9 ÷ 200.0
o
C
Pt100
dP4
0 ÷ 200
o
C
dP5
0 ÷ 400
o
C
dP6
0 ÷ 600
o
C
Jp1
-199.9 ÷ 600.0
o
C
Jp2
-199.9 ÷ 400.0
o
C
JIS
Jp3
-199.9 ÷ 200.0
o
C
Pt50
Jp4
0 ÷ 200
o
C
Jp5
0 ÷ 400
o
C
Jp6
0 ÷ 600
o
C
AN1
An1
-10 ÷ 10 mV
1999 ÷ 9999
AN2
An2
0 ÷ 10 mV
0 ÷ 20 mA w/ 0.5 Ω*
1999 ÷ 9999
AN3
An3
0 ÷ 20 mV
0 ÷ 20 mA w/ 1 Ω*
1999 ÷ 9999
AN4
An4
0 ÷ 50 mV
0 ÷ 20 mA w/ 2.5 Ω*
1999 ÷ 9999
AN5
An5
10 ÷ 50 mV
4 ÷ 20 mA w/ 2.5 Ω*
1999 ÷ 9999
* A 0.5% tolerance resistor should be connected
in parallel with the input.
! If not specially requested, the input is factory configured to type K ( K2).
! To change the input type from thermocouple to RTD or vice-versa, open / close respective jumper pads
on the PCB (see detailed explanation bellow).