8
d2
Derivative time for second control output
60
Range: 0 to 900 s
↓ SET
As for d1
CYt2
output ON / OFF period duration for the second output OUT2
(total time of both ON and OFF periods during PID control)
10
Range: 0 to 150 s
↓ SET
As for CYt1
HYS2
Hysteresis for second output
1
Range: 0 to 1000
↓ SET
As for HYS1
GAP1
Dead band for main output OUT1 (only for two-output controllers)
0
Sets a gap before the set point, in which the output is inactive
↓ SET
If in doubt, set to 0
GAP2
Dead band for second output OUT2 (only for two-output controllers)
0
As for GAP1
↓ SET
If in doubt, set to 0
LCK
Level access control (parameter locking)
0000
See explanation below
↓ SET
over again