8
Use profile S 4 for maximum freedom when making the settings.
Select S 4 and press the key for each confirmation.
if this option has been selected, programming will follow the Flow-Chart below (consult the previous note when changing and confirming
the “n” and “nnn” values):
2.6.1 S4 profile
n CH1
Entry of a value other than zero for the F FtM parameter, under the F nn item,
specifies a time interval in hours after which ventilation will function for 5
minutes, regardless of the temperature present.
This function is available even when ventilation has not been applied to any of
the active channels.
Each channel can have different values for each threshold and ventilation
control can occur with any combination of channels.
Confirmation of “nnn” can be displayed at any moment by pressing the key.
Use the arrow keys to make changes.