Part 1: Operation
16
Overview of code-protected valued
20 => Entry of code no
Enter the correct code number to enable the following
values to be changed
21 => Code number
Reselect a code number
22 => Frost protection temperature (only with outdoor
sensor)
When the outside temperature has dropped below the set
limit value, the heating circuit is switched on and set to the
room temperature of 5°C / 41°F. The hot water
temperature is set to 10°C / 50°F. The boiler is heated to
the value "24 = minimum boiler temperature".
! The outside temperature delay takes effect here.
23 => Hot water short time heating (only with tank
operation)
When the function is activated, the hot water tank is heated
to 65°C / 149°F with every heat-up operation or at least
once a week on Saturdays at 1:00 a.m. to kill off any
bacteria.
24 => Minimum boiler temperature
Used to set a minimum boiler temperature for the heating
operation.
TSP and FHB => (See Pg. 17)
KS OT xxxx
The software number is displayed, and should be used as
a reference for any queries concerning the product.
RETURN Ä =>RETURN to main menu
EXPERT
........ Expert values (see Page15)
20 Enter code no. ----
21 Code No. 1234
22 Frost protection
temperature
(-5)-(+5) => 0°C /
(23)-(41) => 32°F
23 Hot-water short-
time heating
0/1 => 1
24 Min. boiler
temperature
10°C-80°C => 30°C /
50°F-176°F => 86°F
TSP Boiler parameters
FHB Fault history buffer
KS OT 8600 Software number
RETURN