24
Switching on the heating via telephone
The controller can be switched to heating operation
(
B) by means of a telephone switch. The hot water
function, operated by an external hot water tank, is
released for this period.
Connecting a telephone switch:
Connection terminals 3+4.
As soon as these terminals detect a short circuit,
the controller switches to heating operation (with
set room temperature I) and releases the hot water
preparation. When the short circuit is cleared, heating
resumes according to the set mode of operation or the
set heating program.
Technical data
Supply voltage (OT) 15 V DC with
current limitation (13 mA)
Current consumption < 5mA
Type of protection
complying to EN 60529
IP 40
Protection Class II
complying to EN 60730
III
Power reserve of the timer > 10 hours
Permitted ambient
temperature during
operation
0 to 50°C
32 to 122°F
Permitted ambient
temperature for storage
-20 to 60°C
-22 to 140°F
Room sensor
Tolerance in Ohms
Temperature tolerance
Precision resistor NTC
5 kΩ
±-1% at 25 °C/77°F
+/- 0.2 K at 25 °C/77°F
Malfunctions due to improper operation or settings
are not covered by the warranty.
EN 0208 6.6701.360-03 Printed in Germany. All rights reserved.