Part 2: Explanations / Functions Explanation of the set values
19
Room sensor influence: The boiler temperature is
increased by the set value when the room temperature is
1K / 1,8°Ra below that required.
As a result, high values lead to fast regulation with high
fluctuations in the boiler temperature.
0: pure weather-dependent control with room temperature
dependent activation of the heating during the night
reduction.
----: Pure weather-dependent control
Warm-up optimization: Activate the function for the
automatic advance of the time set for starting heating.
Example:
Heating program 6:00 a.m. – 10:30 p.m.
OFF: Heating of the accommodation is set to begin at
6:00 a.m.
ON: Heating is actually started earlier, depending on the
weather and the current room temperature, so that the
accommodation has just reached the set room
temperature at 6:00 a.m.
Maximum time advance: This is the maximum time
heating can be started in advance.
Required time advance: This is the time the start of
heating has been advanced for today (display only).
Adaptation of room sensor: This value can reduce the
following disturbance variables for measuring the room
temperature:
- Production-related deviation of the sensor
- Influence of the temperature of the room wall
- Operating temperature
Outside temperature delay: In the case of extremely well
insulated walls, a change in the outside temperature
affects the room temperature after a correspondingly
longer delay. In the case of weather-dependent control,
this parameter can prevent a premature activation of the
heat generator.(only with outdoor sensor connected
[Terminals 5+6])
Displays: O entering a "1", the room temperature and
set
room temperatures are displayed when the control panel
cover is closed.
Demand-dependent pump control : The pumps and
heating system are switched off if there is no heating
demand. The pumps are reactivated if frost protection is
triggered.
Switch off heating and pumps :
Room regulation: Room temperature > Set temperature
+ 1K
Regulation according to outside temperature: Outside
temperature > Set room temperature + 1K
Switch on:
Room temperature < Set room temperature
or Outside temperature < Set room temperature