Commander SE User Guide 30
Issue Number 8 www.controltechniques.com
High ground leakage current
Most RFI filters have ground leakage current exceeding 3.5mA. All equipment
using these filters must be provided with a permanent fixed ground connection.
Special low-leakage filters are provided for applications where a permanent ground
connection is not practical.
Commander SE Size 1
Table 4.4 Commander SE Size 1
Commander SE Size 2
Table 4.5 Drive Range: SE2D200075 to SE2D200220, single phase
Table 4.6 Drive Range: SE2D200075 to SE2D200220, three phase
Table 4.7 Drive Range: SE23400075 to SE23400400, three phase
WARNING
Motor cable
length
m
Filter and Switching Frequency
Standard
(4200-6102)
Low Cost
(4200-6101)
Low Leakage
(4200-6103)
3kHz 6kHz 12kHz 3kHz 6kHz 12kHz 3kHz 6kHz 12kHz
5 RRRRR I R I #
15 R R I R R I I # #
20 R R I R R I
50 R I I
75 I # #
Motor cable
length
m
Filter and Switching Frequency
Standard
(4200-6201)
Low Cost
(4200-6204)
Low Leakage
(4200-6205)
3kHz 6kHz 12kHz 3kHz 6kHz 12kHz 3kHz 6kHz 12kHz
15 RRR IIIII#
50 R R I
I##
80 R R I
100 I I I
Motor cable
length
m
Filter and Switching Frequency
Standard
(4200-6202)
Low Cost
(4200-6304)
Low Leakage
(4200-6207)
3kHz 6kHz 12kHz 3kHz 6kHz 12kHz 3kHz 6kHz 12kHz
15 RRR
I##II#
45 RRR
I##
100 R R I
Motor cable
length
m
Filter and Switching Frequency
Standard
(4200-6202)
Low Cost
(4200-6304)
Low Leakage
(4200-6207)
3kHz 6kHz 12kHz 3kHz 6kHz 12kHz 3kHz 6kHz 12kHz
15 R R I
I##I##
20 R R I
I##
50 R I I
100 I # #