Commander SE User Guide 30
Issue Number 8 www.controltechniques.com
High ground leakage current
Most RFI filters have ground leakage current exceeding 3.5mA. All equipment
using these filters must be provided with a permanent fixed ground connection.
Special low-leakage filters are provided for applications where a permanent ground
connection is not practical.
Commander SE Size 1
Table 4.4 Commander SE Size 1
Commander SE Size 2
Table 4.5 Drive Range: SE2D200075 to SE2D200220, single phase
Table 4.6 Drive Range: SE2D200075 to SE2D200220, three phase
Table 4.7 Drive Range: SE23400075 to SE23400400, three phase
WARNING
Motor cable
length
m
Filter and Switching Frequency
Standard
(4200-6102)
Low Cost
(4200-6101)
Low Leakage
(4200-6103)
3kHz 6kHz 12kHz 3kHz 6kHz 12kHz 3kHz 6kHz 12kHz
5 RRRRR I R I #
15 R R I R R I I # #
20 R R I R R I
50 R I I
75 I # #
Motor cable
length
m
Filter and Switching Frequency
Standard
(4200-6201)
Low Cost
(4200-6204)
Low Leakage
(4200-6205)
3kHz 6kHz 12kHz 3kHz 6kHz 12kHz 3kHz 6kHz 12kHz
15 RRR IIIII#
50 R R I
I##
80 R R I
100 I I I
Motor cable
length
m
Filter and Switching Frequency
Standard
(4200-6202)
Low Cost
(4200-6304)
Low Leakage
(4200-6207)
3kHz 6kHz 12kHz 3kHz 6kHz 12kHz 3kHz 6kHz 12kHz
15 RRR
I##II#
45 RRR
I##
100 R R I
Motor cable
length
m
Filter and Switching Frequency
Standard
(4200-6202)
Low Cost
(4200-6304)
Low Leakage
(4200-6207)
3kHz 6kHz 12kHz 3kHz 6kHz 12kHz 3kHz 6kHz 12kHz
15 R R I
I##I##
20 R R I
I##
50 R I I
100 I # #

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Control Techniques Commander SE SE53403000 and is the answer not in the manual?

Control Techniques Commander SE SE53403000 Specifications

General IconGeneral
BrandControl Techniques
ModelCommander SE SE53403000
CategoryInverter
LanguageEnglish

Related product manuals