www.controltechniques.com Issue Number: 9
FLC Full load current of the drive (maximum continuous output
current up to 40
o
C ambient temperature). Displayed in Pr 11.32
{0.33}.
I
MAX
A For definition of I
MAX
, see section Types of current range on
page 138.
P
MAX
Where a parameter is represented by a text value, the value in brackets
in the range column is the setting used for serial communications.
Parameter
Range(
Ú)Default(Ö)
Type
Regen Regen
15.01
Supply current magnitude {0.11} ±Maximum drive current A RO Bi P
15.02 Supply voltage {0.12} 400V drive: 0 to 528 V RO Uni P
15.03 Supply power {0.13}
± P
max
kW
RO Bi P
15.04 DC Bus voltage {0.14} 400V drive: 0 to 830 V RO Uni P
15.05 Supply frequency {0.15} ±100 Hz RO Bi P
15.06 Input inductance {0.16} 0.001 to 100 mH RO Uni P
15.07 DC Bus voltage set-point {0.17} 400V drive: 0 to 800 V 400V drive: 700 RW Uni
15.08 Switching frequency {0.18} 3 (0), 4.5 (1), 6 (2), 9 (3), 12 (4) kHz 0 RW Txt P
15.09 High stability space vector modulation {0.19}0 or 1 0RWBit
15.10 Quasi-square operation select {0.20}0 or 1 0RWBit
15.11 Sinusoidal rectifier synchronising {0.21}0 or 1 RO Bit P
15.12 Sinusoidal rectifier synchronised {0.22}0 or 1 RO Bit P
15.13 Sinusoidal rectifier phase loss {0.23}0 or 1 RO Bit P
15.14 Close soft start contactor {0.24}0 or 1 RO Bit P
15.15 Soft start contactor is closed {0.25}0 or 1 RO Bit
15.16 Enable motor drive {0.26}0 or 1 RO Bit P
15.17 Line synchronisation trip enable {0.27}0 or 1 0ROBit
15.18 Line synchronisation status {0.28}
SYNC (0), Ph Det (1), Fr Lo (2), Fr Hi (3),
PLL OI (4), PLL Ph (5)
RO Txt P
15.19 Current control proportional gain 0 to 30,000 110 RW Uni
15.20 Current control integral gain 0 to 30,000 1,000 RW Uni
15.21 Voltage control proportional gain 0 to 30,000 4,000 RW Uni
15.22 Enable extra mains loss detection 0 or 1 0 RW Bit
RO Read Only parameter
Uni Unipolar variable parameter R Reset required for new value to take effect
Bi Bipolar variable parameter S New parameter-value saved at power-down
RW Read / Write parameter
Txt Text variable parameter P Protected; forbidden as destination parameter
Bit Bit parameter FLC Full-load current (max. continuous), Pr
11.32 {0.33}
3I
MAX
×
Pr 5.09
1000
-------------------
×
NOTE

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Control Techniques Unidrive 2403 and is the answer not in the manual?

Control Techniques Unidrive 2403 Specifications

General IconGeneral
BrandControl Techniques
ModelUnidrive 2403
CategoryController
LanguageEnglish

Related product manuals