Service Handbook OGS/OGB
Step 8: Adjust MIN Speed
Instructions:
To adjust the burner for partial load you have to be in the Service programme
in Service point c27/c38 ="Nmax" (!) the value of the MIN speed setting (only
used while measuring the gas exhaust values at partial load!).
Instructions for adjusting the Service point are similar to those in Step 6.
Chart 3: Speed (Start speed = Start)
6.10 6.20 10.10 10.20 12.20 20.10 20.20
HL MIN c26
4800 2800 2800 2800 2800 2800 2800
HL MAX c27
4800 2800 2800 2800 2800 2800 2800
HL START c28
4800 4200 4200 4500 4500 4200 4500
DE MIN c37
4500 4700 3000 3200 3200 3200 3200
DE MAX c38
4500 2800* 3000 3200 3200 3200 3200
DE START c39
4500 2800 3000 3200 3200 3200 3200
* Exception for 6.20 (adjust the Start speed, not the Min speed value)
Step 9: Start burner and measure the gas exhaust values at
MIN speed
Instructions: Start unit and measure gas exhaust values
When adjusting the convection burners Start the Convection programme ;
When adjusting the steam generator burners Start the Steam programme
.
The burner blower runs at the Start speed. After successful ignition of the
burner, it is automatically decreased to MIN speed.
Measure the gas exhaust values, after 1 minute read the measured value and
check with the CO
2
value on Chart 5 "Gas exhaust value @ Min “.
Record the CO
2
and CO values. At a CO value > 500 ppm switch off the unit
and check the cause of the excessive CO value.
Page 8 / 12
Chart 5: Gas exhaust value @ Min
All gas types
O
2
.= 5,5%±0,3%
All gas types
= 1,35±0,02
Erdgas /
Natural Gas
CO
2
= 8,8%±0,1%
LP Gas =
Propan
Butan
CO
2
=
10,3%±0,2%
CO
2
=
11,6%±0,3%
AS/11-2011 / Part No.: 7016396 6_25e_Readjusting the Gas valves_d